ŁK16RG P08 Main disconnector, panel-mounted
Main switch disconnectors panel-mounted ŁK16/25/32 RG P
ŁK#RG\#
EAN:
Standard assemblies are fitted with a switch 2.421
Technical data (continuous work)
Rated insulation voltage Ui | 690 V |
Rated withstand impulse voltage Uimp | 6 kV |
Rated continuous current Iu=Ith | 16 A |
Rated operational power Pe for AC-3 | 5 kW (230 V) 8 kW (400 V) |
Rated operational power Pe for AC-4 | 5 kW (230 V) 7 kW (400 V) |
Rated operational current Ie for AC-3 | 16 A (230 V) 16 A (400 V) |
Rated operational current Ie for AC-4 | 16 A (230 V) 13 A (400 V) |
Rated operational current Ie for DC-21 | 10 A (110 V) 3 A (220 V) |
Short-time short-circuit withstand current Icw(1s) | 0.9 kA |
Rated short-circuit making current Icm | 1.3 kA |
Rated conventional short-circuit current | 13 kA |
Rated current fuse link gG | 16 A |
Ambient temperature | -40 ... +70°C (work) -40 ... +70°C (storage) |
Wire gauge | 1.5...4 mm² |
Protection level: PN-EN 60529 to the panel | IP65 |
Vibration test (acc. to IEC 60068-2-6) | 2...13, 2...100 Hz (frequency) ± 1 mm (acceleration amplitude) ±0.7 g (acceleration amplitude) |
Shock test (acc. to IEC 60068-2-27) | 15 g (peak acceleration) 11 ms (impulse duration) |
Damp heat cyclic test (acc. to IEC 60068-2-30) | 55°C (ambient temperature) 95% (relative humidity) |
Salt mist cyclic test (acc. to IEC 60068-2-52) | severity 1 |