Manual emergency pushbutton OA1 with additional LED
Manual emergency pushbuttons OA1
OA1-W01-#\#-##
EAN:
Code example:
OA1-W01-A-10-24VDC + OP1-1701 P01
Surface mounting, with 1 NO switch. When the glass is broken the button is actuated automatically (type A acc. to PN-EN 54-11). Signalling LED 24 V DC. Plus another signalling LED 24 V DC.
Manual emergency pushbutton OA1 with double LED signalling can indicate two system states. LEDs have separate "+" "-" terminals. LEDs can be connected to the system directly or via switches (NO or NC) typically installed in the enclosure. When ordering, please use the standard ordering code for the version with single signalling and additionally order the second LED. If additional markings are required, e.g. Alarm, Fire, System Failure, System OK or others, please fill in the order form for a manual emergency pushbutton OA1 with double signalling. Owners of the manual emergency pushbutton OA1 (only surface mounting version W01) with a masking plate suitable for mounting 2 LEDs can order additional LED signalization and new front panel labels.
NOTE: OA1 with double signalling is only available in W01 version (surface mounting).
NOTE: OA1 with double signalling is only available in W01 version (surface mounting).
When selecting current paths, the selected type (A or B) should be taken into account
TYP A
NO contacts (10, 20, 30): after breaking the glass or removing the cover, the contacts open.
NC contacts (01, 02, 03): after breaking the glass or removing the cover, the contacts close.
Mixed NC/NO contacts (11, 12, 21): after breaking the glass, the NO contacts will open and the NC contacts will close.
TYP B
NO contacts (10, 20, 30): after breaking the glass or removing the cover, the button must be pressed manually - the contacts will close.
NC contacts (01, 02, 03): after breaking the glass or removing the cover, the button must be pressed manually - the contacts will open.
Mixed NC/NO contacts (11, 12, 21): after pressing the button, the NO contacts will close and the NC contacts will open.
TYP A
NO contacts (10, 20, 30): after breaking the glass or removing the cover, the contacts open.
NC contacts (01, 02, 03): after breaking the glass or removing the cover, the contacts close.
Mixed NC/NO contacts (11, 12, 21): after breaking the glass, the NO contacts will open and the NC contacts will close.
TYP B
NO contacts (10, 20, 30): after breaking the glass or removing the cover, the button must be pressed manually - the contacts will close.
NC contacts (01, 02, 03): after breaking the glass or removing the cover, the button must be pressed manually - the contacts will open.
Mixed NC/NO contacts (11, 12, 21): after pressing the button, the NO contacts will close and the NC contacts will open.
Rated insulation voltage Ui | 500 V |
Rated continuous current Iu=Ith | 10 A |
Rated operational current Ie for AC-15 | 2.5 A (230 V) 1.6 A (400/500 V) |
Rated operational current Ie for AC-13 | 4 A (24 V) 1 A (110 V) 0.25 A (220 V) |
Degree of protection | IP65 |
Wire gauge | 2× 1...2.5 mm² (solid) 2× 0.75...1.5 mm² (stranded) |
2LED7 | C230VAC+Z230VAC |
2LED8 | C230VAC+Z24VDC |
2LED10 | C24VDC+Z230VAC |
2LED11 | C24VDC+Z24VDC |
2LED7 | C230VAC+Z230VAC |
2LED8 | C230VAC+Z24VDC |
2LED10 | C24VDC+Z230VAC |
2LED11 | C24VDC+Z24VDC |