Manual call point OP1 with additional LED

Manual call point OP1 with additional LED

Manual call points OP1

OP1-W01-#\#-##

Code example:
OP1-W01-A-10-24VDC + OP1-1701 P01
Surface mounting, with 1 NO switch. When the glass is broken the button is actuated automatically (type A acc. to PN-EN 54-11). Signalling LED 24 V DC. Plus another signalling LED 24 V DC.

Manual call point OP1 with double LED signalling can indicate two system states. LEDs have separate "+" "-" terminals. LEDs can be connected to the system directly or via switches (NO or NC) typically installed in the enclosure. When ordering, please use the standard ordering code for the version with single signalling and additionally order the second LED. If additional markings are required, e.g. Alarm, Fire, System Failure, System OK or others, please fill in the order form for a manual call point OP1 with double signalling. Owners of the manual call point OP1 (only surface mounting version W01) with a masking plate suitable for mounting 2 LEDs can order additional LED signalization and new front panel labels.
NOTE: OP1 with double signalling is only available in W01 version (surface mounting).
When selecting current paths, the selected type (A or B) should be taken into account
TYP A
NO contacts (10, 20, 30): after breaking the glass or removing the cover, the contacts open.
NC contacts (01, 02, 03): after breaking the glass or removing the cover, the contacts close.
Mixed NC/NO contacts (11, 12, 21): after breaking the glass, the NO contacts will open and the NC contacts will close.
TYP B
NO contacts (10, 20, 30): after breaking the glass or removing the cover, the button must be pressed manually - the contacts will close.
NC contacts (01, 02, 03): after breaking the glass or removing the cover, the button must be pressed manually - the contacts will open.
Mixed NC/NO contacts (11, 12, 21): after pressing the button, the NO contacts will close and the NC contacts will open.
Rated insulation voltage Ui 500 V
Rated continuous current Iu=Ith 10 A
Rated operational current Ie for AC-15 2.5 A (230 V)
1.6 A (400/500 V)
Rated operational current Ie for AC-13 4 A (24 V)
1 A (110 V)
0.25 A (220 V)
Degree of protection IP65 – declared by the manufacturer (the selected feature of the product was not confirmed by CNBOP-PIB)
OP1 is properly protected against water according to the standard: PN-EN60068-2-30
Wire gauge 2× 1...2.5 mm² (solid)
2× 0.75...1.5 mm² (stranded)
2LED7 C230VAC+Z230VAC
2LED8 C230VAC+Z24VDC
2LED10 C24VDC+Z230VAC
2LED11 C24VDC+Z24VDC
2LED7 C230VAC+Z230VAC
2LED8 C230VAC+Z24VDC
2LED10 C24VDC+Z230VAC
2LED11 C24VDC+Z24VDC

Dimensions

  • Manual call point OP1 with additional LED - Dimensions

    surface mounting

Reference

Download